Combiner box sizing calculator

Enter your string count and panel Isc. Get the correct per-string fuse rating and the combiner box's required busbar size.

Your numbers

1 Project details Optional
Shown on your exported report. Leave blank to skip.
2 Array specs
Combiner boxes typically make sense once you have 3 or more strings.
Short circuit current, from the panel datasheet.

How it works

Three steps to your combiner box sizing

Step 1

Confirm your string count first

If you haven't finalized your string layout, the MPPT count vs array layout calculator and string sizing tool can help settle that before sizing the combiner.

Step 2

Pull panel Isc from the datasheet

Every string using the same panel model shares this figure, so you only need to look it up once.

Step 3

Check both the fuse and the busbar

These are two separate sizing questions. Getting the fuse right doesn't automatically mean the busbar is sized correctly, and vice versa.

Understanding combiner box sizing

Why a combiner box exists at all

Once an array has more strings than an inverter's MPPT inputs can directly accept, or when strings need to be combined before reaching a single feed to a disconnect or inverter, a combiner box brings multiple strings together into one output. Each incoming string gets its own individually fused input, and the box's output busbar carries the combined current of all strings at once, a layout question the MPPT count vs array layout calculator helps plan out first, alongside confirming your actual string count with the string length vs panel count calculator.

Why each string needs its own fuse

Without individual fusing, a fault in one string could allow current to backfeed from the other parallel strings through the faulted one, potentially exceeding the wiring's safe current rating and creating a fire risk. NEC 690.9 addresses this by requiring overcurrent protection sized specifically for PV source circuits, using the 1.56 factor applied to each string's Isc rather than a simpler rule of thumb, with the underlying conductor ampacity limits coming from NEC Table 310.16.

Why the busbar calculation is separate from the fuse calculation

Each string's fuse only needs to protect that single string's wiring from an internal fault. The combiner's output busbar, by contrast, needs to safely carry the sum of every string's current flowing through it simultaneously under normal operation, which is a fundamentally different sizing question using the same 125% continuous current principle covered in the parallel strings current calculator.

What happens with mismatched string sizes

This calculator assumes every string uses the same panel model and Isc rating, which is the most common residential and light commercial scenario. If your design mixes different panel models or wattages across strings, each string's fuse needs to be sized individually against its own actual Isc, and the busbar calculation needs to sum each string's real current rather than multiplying one Isc figure by string count. The string mismatch loss calculator can help quantify how much output that mismatch actually costs you, separate from the fusing question here.

Choosing a combiner box product that fits

Once you know your required fuse size and busbar rating, check that against the specific combiner box product's specifications, since manufacturers offer models with varying numbers of fused inputs and different maximum busbar ratings. A box rated for exactly your calculated numbers leaves no room for future string additions, so many installers choose a model with some headroom above the immediate requirement, similar to the downstream sizing covered in the wire gauge sizing calculator. NREL's PVWatts calculator can help confirm the array-level production numbers behind whichever sizing you land on.

Questions

Frequently asked

Multiply the panel's short circuit current, Isc, by 1.56, then round up to the nearest standard fuse size. A panel with an 11A Isc needs a fuse rated at least 17.16A, which rounds up to a standard 20A fuse.

The 1.56 factor combines two separate 125% factors commonly applied together in NEC 690.9 fuse sizing guidance: one for continuous current and one as an additional safety margin specific to overcurrent protection in PV source circuits, rather than the single 125% factor used for simpler current checks elsewhere.

The busbar carries the combined current of every string at once, so it's sized from the sum of all strings' Isc with a 125% continuous current factor applied, then rounded up to a standard busbar rating, separate from each individual string's own fuse rating.

Usually not. A small array with only one or two strings often connects directly to the inverter's MPPT inputs without a separate combiner box, since combining is really only necessary once the number of strings exceeds what an inverter's inputs can accept directly.